西门子 CPU1511F-1PN S7-1500F
1233.00
上海松江区
上海励辉自动化科技有限公司
3年 | 指数:70 | 工商已认证
店铺推荐
  • 图文详情
  • 产品参数
西门子 CPU1511F-1PN S7-1500F 

概述

  • Entry-level CPU in the S7-1500F Controller product range
  • Can be used for safety functions up to SIL 3 according to IEC 61508 and up to PLe according to ISO 13849
  • Suitable for standard and fail-safe applications with medium requirements for program scope and processing speed
  • Used as central controller in production lines with central and distributed I/O
  • Supports PROFIsafe in centralized and distributed configurations 
  • PROFINET IO IRT interface with 2-port switch
  • PROFINET IO controller for operating distributed I/O on PROFINET
  • PROFINET I-Device for connecting the CPU as an intelligent PROFINET device under a SIMATIC or non-Siemens PROFINET I/O controller
  • Isochronous mode

Note:
SIMATIC Memory Card required for operation of the CPU



应用

The CPU 1511-1 PN is the cost-effective entry-level CPU for standard and fail-safe applications with medium requirements for processing speed and speed of response in discrete production technology. With its work memory size, this CPU is also suitable for medium-sized applications. It can be used as a PROFINET IO controller or as distributed intelligence (PROFINET I-Device). The integrated PROFINET IO IRT interface is designed as a 2-port switch, enabling a linear topology to be set up in the system. In addition, the CPU offers comprehensive control functionalities via easy-to-configure blocks as well as the ability to connect drives via standardized PLCopen blocks.



设计

The CPU 1511F-1 PN has:

  • A powerful processor:
    The CPU achieves a command execution time as low as 60 ns per binary command.
  • Extensive work memory:
    230 KB for program, 1 MB for data
  • SIMATIC Memory Cards as load memory;
    permit additional functions such as datalog and archives
  • Flexible expansion options: single-tier configuration with max. 32 modules (CPU + 31 modules)
  • Display with functions for
    • Display of overview information such as station name, higher level designation, location designation, etc.
    • Showing diagnostic information
    • Showing module information
    • Showing display settings
    • Setting IP addresses
    • Setting date and time
    • Switching the operating mode
    • Resetting the CPU to factory settings
    • Disabling/enabling the display
    • Enabling of protection levels
    • Display of safety mode, overall signature and date of the last download with signature change
  • PROFINET IO IRT interface for connecting distributed I/O via PROFINET
  • Supports PROFIsafe in centralized and distributed configuration


功能

  • Performance
    • Faster command processing, depending on the CPU type, language extensions and new data types
    • Even shorter response times of the CPUs due to considerably faster backplane bus
    • Powerful network connection:
      Each CPU is equipped with PROFINET IO IRT (2-port switch) as standard interface.
  • Integrated technology
    • Connection of analog and PROFIdrive-capable drives via standardized blocks (PLCopen)
    • Support of speed-controlled and positioning axes as well as external encoders
    • Trace functions for all CPU tags, both for diagnostics in real time and for sporadic error detection
    • Comprehensive control functionalities, e.g. easily configurable blocks for automatic optimization of the control parameters for optimum control quality
  • Security Integrated
    • Password-based know-how protection against unauthorized read-out and modification of program blocks
    • Copy protection for tying individual blocks to the serial number of the SIMATIC Memory Card: The block can only run if the configured memory card is inserted in the CPU.
    • 4-level authorization concept:
      Communication to operator panels can also be restricted.
    • Manipulation protection:
      The controller recognizes changed or unauthorized transmissions of the engineering data.
  • Design and handling
    • Display of overview information:
      E.g. Station name, plant designation, location identifier, etc., diagnostic information, module information, display settings.
    • Possible operations on the display:
      Set addresses, set date and time, select operating mode of CPU, reset CPU to factory settings, disable/enable display, activate protection levels.
  • Integrated system diagnostics
    • System diagnostics information is displayed consistently and in plain text in the display, TIA Portal, operator panels and web server, even for messages from the drives, and updated even if the CPU is in STOP mode.
    • Integrated in the firmware of the CPU, no special configuration is required
  • SIMATIC Memory Card (required for operation of the CPU)
    • Used as plug-in load memory or for updating the firmware.
    • Also for storing additional documents or csv files (for recipes and archives)
    • Creation of data blocks for storage/reading of data via SFCs of the user program
  • Datalog (archives) and recipes
    • Storage of csv files for recipes and archives on the SIMATIC Memory Card;
      easy access to plant-relevant operating data using Office tools and via web server
    • Easy access to configuration data of the machine by means of a web browser or SD card reader (two-way data exchange from and to the PLC)
  • Programming of the standard program section
    • Programming as of STEP 7 V12 SP1
  • Programming of the fail-safe program section
    • Programming of the safety-related program section with the "STEP 7 Safety Advanced" option package. STEP 7 Safety Advanced V12 can run under SIMATIC STEP 7 Professional V12 SP1.


技术规范

Article number

6ES7511-1FK02-0AB0

 

CPU 1511F-1PN, 225KB prog, 1MB data

General information

 

Product type designation

CPU 1511F-1 PN

HW functional status

FS03

Firmware version

V2.9

Product function

 

  • ● I&M data

Yes; I&M0 to I&M3

  • ● Isochronous mode

Yes; Distributed and central; with minimum OB 6x cycle of 625 µs (distributed) and 1 ms (central)

Engineering with

 

  • ● STEP 7 TIA Portal configurable/integrated from version

V17 (FW V2.9) / V15 (FW V2.5) or higher; with older TIA Portal versions configurable as 6ES7511-1FK01-0AB0

Configuration control

 

via dataset

Yes

Display

 

Screen diagonal [cm]

3.45 cm

Control elements

 

Number of keys

8

Mode buttons

2

Supply voltage

 

Rated value (DC)

24 V

permissible range, lower limit (DC)

19.2 V

permissible range, upper limit (DC)

28.8 V

Reverse polarity protection

Yes

Mains buffering

 

  • ● Mains/voltage failure stored energy time

5 ms

  • ● Repeat rate, min.

1/s

Input current

 

Current consumption (rated value)

0.7 A

Current consumption, max.

0.95 A

Inrush current, max.

1.9 A; Rated value

I²t

0.02 A²·s

Power

 

Infeed power to the backplane bus

10 W

Power consumption from the backplane bus (balanced)

5.5 W

Power loss

 

Power loss, typ.

5.7 W

Memory

 

Number of slots for SIMATIC memory card

1

SIMATIC memory card required

Yes

Work memory

 

  • ● integrated (for program)

225 kbyte

  • ● integrated (for data)

1 Mbyte

Load memory

 

  • ● Plug-in (SIMATIC Memory Card), max.

32 Gbyte

Backup

 

  • ● maintenance-free

Yes

CPU processing times

 

for bit operations, typ.

60 ns

for word operations, typ.

72 ns

for fixed point arithmetic, typ.

96 ns

for floating point arithmetic, typ.

384 ns

CPU-blocks

 

Number of elements (total)

4 000; Blocks (OB, FB, FC, DB) and UDTs

DB

 

  • ● Number range

1 ... 60 999; subdivided into: number range that can be used by the user: 1 ... 59 999, and number range of DBs created via SFC 86: 60 000 ... 60 999

  • ● Size, max.

1 Mbyte; For DBs with absolute addressing, the max. size is 64 KB

FB

 

  • ● Number range

0 ... 65 535

  • ● Size, max.

150 kbyte

FC

 

  • ● Number range

0 ... 65 535

  • ● Size, max.

150 kbyte

OB

 

  • ● Size, max.

150 kbyte

  • ● Number of free cycle OBs

100

  • ● Number of time alarm OBs

20

  • ● Number of delay alarm OBs

20

  • ● Number of cyclic interrupt OBs

20; With minimum OB 3x cycle of 500 µs

  • ● Number of process alarm OBs

50

  • ● Number of DPV1 alarm OBs

3

  • ● Number of isochronous mode OBs

2

  • ● Number of technology synchronous alarm OBs

2

  • ● Number of startup OBs

100

  • ● Number of asynchronous error OBs

4

  • ● Number of synchronous error OBs

2

  • ● Number of diagnostic alarm OBs

1

Nesting depth

 

  • ● per priority class

24; Up to 8 possible for F-blocks

Counters, timers and their retentivity

 

S7 counter

 

  • ● Number

2 048

Retentivity

 

  • — adjustable

Yes

IEC counter

 

  • ● Number

Any (only limited by the main memory)

Retentivity

 

  • — adjustable

Yes

S7 times

 

  • ● Number

2 048

Retentivity

 

  • — adjustable

Yes

IEC timer

 

  • ● Number

Any (only limited by the main memory)

Retentivity

 

  • — adjustable

Yes

Data areas and their retentivity

 

Retentive data area (incl. timers, counters, flags), max.

128 kbyte; In total; available retentive memory for bit memories, timers, counters, DBs, and technology data (axes): 88 KB

Extended retentive data area (incl. timers, counters, flags), max.

1 Mbyte; When using PS 6 0W 24/48/60 V DC HF

Flag

 

  • ● Size, max.

16 kbyte

  • ● Number of clock memories

8; 8 clock memory bit, grouped into one clock memory byte

Data blocks

 

  • ● Retentivity adjustable

Yes

  • ● Retentivity preset

No

Local data

 

  • ● per priority class, max.

64 kbyte; max. 16 KB per block

Address area

 

Number of IO modules

1 024; max. number of modules / submodules

I/O address area

 

  • ● Inputs

32 kbyte; All inputs are in the process image

  • ● Outputs

32 kbyte; All outputs are in the process image

per integrated IO subsystem

 

  • — Inputs (volume)

8 kbyte

  • — Outputs (volume)

8 kbyte

per CM/CP

 

  • — Inputs (volume)

8 kbyte

  • — Outputs (volume)

8 kbyte

Subprocess images

 

  • ● Number of subprocess images, max.

32

Hardware configuration

 

Number of distributed IO systems

32; A distributed I/O system is characterized not only by the integration of distributed I/O via PROFINET or PROFIBUS communication modules, but also by the connection of I/O via AS-i master modules or links (e.g. IE/PB-Link)

Number of DP masters

 

  • ● Via CM

4; A maximum of 4 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total

Number of IO Controllers

 

  • ● integrated

1

  • ● Via CM

4; A maximum of 4 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total

Rack

 

  • ● Modules per rack, max.

32; CPU + 31 modules

  • ● Number of lines, max.

1

PtP CM

 

  • ● Number of PtP CMs

the number of connectable PtP CMs is only limited by the number of available slots

Time of day

 

Clock

 

  • ● Type

Hardware clock

  • ● Backup time

6 wk; At 40 °C ambient temperature, typically

  • ● Deviation per day, max.

10 s; Typ.: 2 s

Operating hours counter

 

  • ● Number

16

Clock synchronization

 

  • ● supported

Yes

  • ● in AS, master

Yes

  • ● in AS, slave

Yes

  • ● on Ethernet via NTP

Yes

Interfaces

 

Number of PROFINET interfaces

1

1. Interface

 

Interface types

 

  • ● RJ 45 (Ethernet)

Yes; X1

  • ● Number of ports

2

  • ● integrated switch

Yes

Protocols

 

  • ● IP protocol

Yes; IPv4

  • ● PROFINET IO Controller

Yes

  • ● PROFINET IO Device

Yes

  • ● SIMATIC communication

Yes

  • ● Open IE communication

Yes; Optionally also encrypted

  • ● Web server

Yes

  • ● Media redundancy

Yes; MRP Automanager according to IEC 62439-2 Edition 2.0

PROFINET IO Controller

 

Services

 

  • — PG/OP communication

Yes

  • — Isochronous mode

Yes

  • — Direct data exchange

Yes; Requirement: IRT and isochronous mode (MRPD optional)

  • — IRT

Yes

  • — PROFIenergy

Yes; per user program

  • — Prioritized startup

Yes; Max. 32 PROFINET devices

  • — Number of connectable IO Devices, max.

128; In total, up to 256 distributed I/O devices can be connected via AS-i, PROFIBUS or PROFINET

  • — Of which IO devices with IRT, max.

64

  • — Number of connectable IO Devices for RT, max.

128

  • — of which in line, max.

128

  • — Number of IO Devices that can be simultaneously activated/deactivated, max.

8; in total across all interfaces

  • — Number of IO Devices per tool, max.

8

  • — Updating times

The minimum value of the update time also depends on communication share set for PROFINET IO, on the number of IO devices, and on the quantity of configured user data

Update time for IRT

 

  • — for send cycle of 250 µs

250 μs to 4 ms; Note: In the case of IRT with isochronous mode, the minimum update time of 625 µs of the isochronous OB is decisive

  • — for send cycle of 500 µs

500 μs to 8 ms; Note: In the case of IRT with isochronous mode, the minimum update time of 625 µs of the isochronous OB is decisive

  • — for send cycle of 1 ms

1 ms to 16 ms

  • — for send cycle of 2 ms

2 ms to 32 ms

  • — for send cycle of 4 ms

4 ms to 64 ms

  • — With IRT and parameterization of "odd" send cycles

Update time = set "odd" send clock (any multiple of 125 µs: 375 µs, 625 µs ... 3 875 µs)

Update time for RT

 

  • — for send cycle of 250 µs

250 µs to 128 ms

  • — for send cycle of 500 µs

500 µs to 256 ms

  • — for send cycle of 1 ms

1 ms to 512 ms

  • — for send cycle of 2 ms

2 ms to 512 ms

  • — for send cycle of 4 ms

4 ms to 512 ms

PROFINET IO Device

 

Services

 

  • — PG/OP communication

Yes

  • — Isochronous mode

No

  • — IRT

Yes

  • — PROFIenergy

Yes; per user program

  • — Shared device

Yes

  • — Number of IO Controllers with shared device, max.

4

  • — activation/deactivation of I-devices

Yes; per user program

  • — Asset management record

Yes; per user program

Interface types

 

RJ 45 (Ethernet)

 

  • ● 100 Mbps

Yes

  • ● Autonegotiation

Yes

  • ● Autocrossing

Yes

  • ● Industrial Ethernet status LED

Yes

Protocols

 

PROFIsafe

Yes; V2.4 / V2.6

Number of connections

 

  • ● Number of connections, max.

96; via integrated interfaces of the CPU and connected CPs / CMs

  • ● Number of connections reserved for ES/HMI/web

10

  • ● Number of connections via integrated interfaces

64

  • ● Number of S7 routing paths

16

Redundancy mode

 

  • ● H-Sync forwarding

Yes

Media redundancy

 

  • — Media redundancy

only via 1st interface (X1)

  • — MRP

Yes; MRP Automanager according to IEC 62439-2 Edition 2.0, MRP Manager; MRP Client

  • — MRP interconnection, supported

Yes; as MRP ring node according to IEC 62439-2 Edition 3.0

  • — MRPD

Yes; Requirement: IRT

  • — Switchover time on line break, typ.

200 ms; For MRP, bumpless for MRPD

  • — Number of stations in the ring, max.

50

SIMATIC communication

 

  • ● PG/OP communication

Yes; encryption with TLS V1.3 pre-selected

  • ● S7 routing

Yes

  • ● S7 communication, as server

Yes

  • ● S7 communication, as client

Yes

  • ● User data per job, max.

See online help (S7 communication, user data size)

Open IE communication

 

  • ● TCP/IP

Yes

  • — Data length, max.

64 kbyte

  • — several passive connections per port, supported

Yes

  • ● ISO-on-TCP (RFC1006)

Yes

  • — Data length, max.

64 kbyte

  • ● UDP

Yes

  • — Data length, max.

2 kbyte; 1 472 bytes for UDP broadcast

  • — UDP multicast

Yes; Max. 5 multicast circuits

  • ● DHCP

Yes

  • ● DNS

Yes

  • ● SNMP

Yes

  • ● DCP

Yes

  • ● LLDP

Yes

  • ● Encryption

Yes; Optional

Web server

 

  • ● HTTP

Yes; Standard and user pages

  • ● HTTPS

Yes; Standard and user pages

OPC UA

 

  • ● Runtime license required

Yes

  • ● OPC UA Client

Yes

  • — Application authentication

Yes

  • — Security policies

Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256

  • — User authentication

"anonymous" or by user name & password

  • — Number of connections, max.

4

  • — Number of nodes of the client interfaces, max.

1 000

  • — Number of elements for one call of OPC_UA_NodeGetHandleList/OPC_UA_ReadList/OPC_UA_WriteList, max.

300

  • — Number of elements for one call of OPC_UA_NameSpaceGetIndexList, max.

20

  • — Number of elements for one call of OPC_UA_MethodGetHandleList, max.

100

  • — Number of simultaneous calls of the client instructions per connection (except OPC_UA_ReadList,OPC_UA_WriteList,OPC_UA_MethodCall), max.

1

  • — Number of simultaneous calls of the client instructions OPC_UA_ReadList,OPC_UA_WriteList and OPC_UA_MethodCall, max.

5

  • — Number of registerable nodes, max.

5 000

  • — Number of registerable method calls of OPC_UA_MethodCall, max.

100

  • — Number of inputs/outputs when calling OPC_UA_MethodCall, max.

20

  • ● OPC UA Server

Yes; Data access (read, write, subscribe), method call, custom address space

  • — Application authentication

Yes

  • — Security policies

Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256

  • — User authentication

"anonymous" or by user name & password

  • — Number of sessions, max.

32

  • — Number of accessible variables, max.

50 000

  • — Number of registerable nodes, max.

10 000

  • — Number of subscriptions per session, max.

20

  • — Sampling interval, min.

100 ms

  • — Publishing interval, min.

500 ms

  • — Number of server methods, max.

20

  • — Number of inputs/outputs per server method, max.

20

  • — Number of monitored items, max.

1 000; for 1 s sampling interval and 1 s send interval

  • — Number of server interfaces, max.

10 of each "Server interfaces" / "Companion specification" type and 20 of the type "Reference namespace"

  • — Number of nodes for user-defined server interfaces, max.

1 000

Further protocols

 

  • ● MODBUS

Yes; MODBUS TCP

Isochronous mode

 

Equidistance

Yes

S7 message functions

 

Number of login stations for message functions, max.

32

Program alarms

Yes

Number of configurable program messages, max.

5 000; Program messages are generated by the "Program_Alarm" block, ProDiag or GRAPH

Number of loadable program messages in RUN, max.

2 500

Number of simultaneously active program alarms

 

  • ● Number of program alarms

600

  • ● Number of alarms for system diagnostics

100

  • ● Number of alarms for motion technology objects

80

Test commissioning functions

 

Joint commission (Team Engineering)

Yes; Parallel online access possible for up to 5 engineering systems

Status block

Yes; Up to 8 simultaneously (in total across all ES clients)

Single step

No

Number of breakpoints

8

Status/control

 

  • ● Status/control variable

Yes; without fail-safe

  • ● Variables

inputs/outputs, bit memories, DBs, peripheral I/Os (without fail-safe), times, counters

  • ● Number of variables, max.

 

  • — of which status variables, max.

200; per job

  • — of which control variables, max.

200; per job

Forcing

 

  • ● Forcing

Yes; without fail-safe

  • ● Forcing, variables

peripheral inputs/outputs (without fail-safe)

  • ● Number of variables, max.

200

Diagnostic buffer

 

  • ● present

Yes

  • ● Number of entries, max.

1 000

  • — of which powerfail-proof

500

Traces

 

  • ● Number of configurable Traces

4; Up to 512 KB of data per trace are possible

Interrupts/diagnostics/status information

 

Diagnostics indication LED

 

  • ● RUN/STOP LED

Yes

  • ● ERROR LED

Yes

  • ● MAINT LED

Yes

  • ● STOP ACTIVE LED

Yes

  • ● Connection display LINK TX/RX

Yes

Supported technology objects

 

Motion Control

Yes; Note: The number of technology objects affects the cycle time of the PLC program; selection guide via the TIA Selection Tool

  • ● Number of available Motion Control resources for technology objects

800

  • ● Required Motion Control resources

 

  • — per speed-controlled axis

40

  • — per positioning axis

80

  • — per synchronous axis

160

  • — per external encoder

80

  • — per output cam

20

  • — per cam track

160

  • — per probe

40

  • ● Positioning axis

 

  • — Number of positioning axes at motion control cycle of 4 ms (typical value)

5

  • — Number of positioning axes at motion control cycle of 8 ms (typical value)

10

Controller

 

  • ● PID_Compact

Yes; Universal PID controller with integrated optimization

  • ● PID_3Step

Yes; PID controller with integrated optimization for valves

  • ● PID-Temp

Yes; PID controller with integrated optimization for temperature

Counting and measuring

 

  • ● High-speed counter

Yes

Standards, approvals, certificates

 

Highest safety class achievable in safety mode

 

  • ● Performance level according to ISO 13849-1

PLe

  • ● SIL acc. to IEC 61508

SIL 3

Probability of failure (for service life of 20 years and repair time of 100 hours)

 

  • — Low demand mode: PFDavg in accordance with SIL3

< 2.00E-05

  • — High demand/continuous mode: PFH in accordance with SIL3

< 1.00E-09

Ambient conditions

 

Ambient temperature during operation

 

  • ● horizontal installation, min.

-25 °C; No condensation

  • ● horizontal installation, max.

60 °C; Display: 50 °C, at an operating temperature of typically 50 °C, the display is switched off

  • ● vertical installation, min.

-25 °C; No condensation

  • ● vertical installation, max.

40 °C; Display: 40 °C, at an operating temperature of typically 40 °C, the display is switched off

Ambient temperature during storage/transportation

 

  • ● min.

-40 °C

  • ● max.

70 °C

Altitude during operation relating to sea level

 

  • ● Installation altitude above sea level, max.

5 000 m; Restrictions for installation altitudes > 2 000 m, see manual

configuration / header

 

configuration / programming / header

 

Programming language

 

  • — LAD

Yes; incl. failsafe

  • — FBD

Yes; incl. failsafe

  • — STL

Yes

  • — SCL

Yes

  • — GRAPH

Yes

Know-how protection

 

  • ● User program protection/password protection

Yes

  • ● Copy protection

Yes

  • ● Block protection

Yes

Access protection

 

  • ● Password for display

Yes

  • ● Protection level: Write protection

Yes; Specific write protection both for Standard and for Failsafe

  • ● Protection level: Read/write protection

Yes

  • ● Protection level: Write protection for Failsafe

Yes

  • ● Protection level: Complete protection

Yes

programming / cycle time monitoring / header

 

  • ● lower limit

adjustable minimum cycle time

  • ● upper limit

adjustable maximum cycle time

Dimensions

 

Width

35 mm

Height

147 mm

Depth

129 mm

Weights

 

Weight, approx.

405 g


 