倍加福安全栅KCD2-RR2-EX1 General specifications |
Signal type |
Analog input |
Functional safety related parameters |
Safety Integrity Level (SIL) |
SIL 2 |
Supply |
Connection |
Power Rail or terminals 9+, 10- |
Rated voltage |
19 ... 30 V DC |
Ripple |
within the supply tolerance |
Rated current |
< 20 mA |
Power consumption |
0.35 W (24 V and 1 mA sense current) |
倍加福安全栅KCD2-RR2-EX1 Input |
Connection side |
field side |
Connection |
terminals 1, 2, 3, 4 |
Line fault detection |
yes , at Pt100 |
Lead resistance |
≤ 10 % of resistance value |
Transmission range |
0 ... 10 mA |
Available voltage |
9 V |
Line fault detection |
8 nA |
倍加福安全栅KCD2-RR2-EX1 Output |
Connection side |
control side |
Connection |
terminals 5-, 7-, 6+, 8+ |
Current |
0 ... 10 mA |
Available voltage |
0 ... 4.2 V |
Fault signal |
< 10 Ω or > 400 Ω, depending on lead disconnected (measuring current ≤ 1 mA)