BXM(D)防爆动力配电箱
一、防爆动力配电箱适用范围 Explosion-proof power distribution box applicable scope
1. 爆炸性气体环境危险场所:1区、2区;
2. 可燃性气体、蒸气级别:ⅡA、ⅡB;
3. 温度组别:T1~T4;
4. 户内、户外(IP54)。
1. For the dangerous sites with explosive air mixture: 1 division, 2 division;
2. Flammable gas, steam class: ⅡA、ⅡB;
3. Temperatures classification: T1~T4;
4. Indoor and outdoor (IP54).
二、防爆动力配电箱产品特点 Explosion-proof power distribution box product features
1. 本产品为复合型,开关箱采用隔爆型结构,母线箱及出线箱采用增按型结构。
2. 铸铝合金外壳,内装高分断小型断路器或塑壳式断路器。有C45、C65、CM1可供选择。
3. 具有过载短路保护功能。
4. 有特殊要求可特制。
5. 钢管或电缆布线均可。
1. The box is of combined type, its switch compartment is of explosion-proof structure, busbar and outlet compartment adopt safety-increased structure.
2. The shell is made of diecasted Al-alloy, inside is installed MCB or MCCB. Has C45, C65, CM1 to be supplied.
3. With protections of overload and short-circuit.
4. Special type can be made.
5. Suitable for both steel pipe and cable wiring.
三、防爆动力配电箱技术参数 Explosion-proof power distribution box technical parameters
1.执行标准:GB3836.1.2.3-2000/IEC60079
2.防爆标志:ExdeIIBT6*ExdeIICT6
3.额定电压:AC380V/220V/50HZ
4.主回路额定电流:60A-400A
5.防护等级:IP55
6.防腐等级:WF1
1. Executive standard: GB3836.1.2.3-2000 / IEC60079
2. ExdeIIBT6 * symbol: ExdeIICT6 explosion
3. The rated voltage: AC380V / 220V / 50HZ
4. The main circuit rated current: 60A - 400A
5. Protection level: IP55
6. The anti-corrosion class: WF1
四、防爆动力配电箱订货须知 Explosion-proof power distribution box order guidelines
1.订货时应注明配电箱的支路数,各支路相应的电流以及断路器的级数,若需带漏电保护功能请注明;
2.如需带总开关则请注明总开关的电流及级数,并注明进出线方向,进出线规格及对应数量;
3.BXM(D)81防爆动力配电箱,可根据用户要求进行特殊设计,用户需提供电器系统图;
1. If ordering indicate the imlet distribution box, each branch corresponding current and breaker series, if need to take leakage protection function please indicate;
2. If you need take chief switch, please indicate the master switch, and the current and series in the direction indicated, into outlet specifications qualify and the corresponding quantity;
3. BXM (D) 81 explosion-proof power distribution box according to user requirements for special design, user must provide electrical system graph;